符合ROHS标准,CE认证
Service: Air andnon-combustible, compatible gases.
Wetted Materials: DiaphragmMaterial: Silicone. Housing Material: Switch Body: PA 6.6 and POM;Cover: Polystyrene.
Temperature Limits: Processambient temperature from -4 to 185°F (-20 to 85°C).
Pressure Limits: Max.Operating Pressure: 40" w.c. (10 kPa) for all pressureranges.
Switch Type: Single-poledouble-throw (SPDT).
Electrical Rating: Standard:Max., 1.5A/250 VAC, max. switching rate: 6 cycles/min.; GoldContact Option: 0.4 A/ 250 VAC.
Electrical Connections:Push-on screw terminals. M20x1.5 with cable strain relief oroptional 1/2" NPT connection.
Process Connections: 5/16"(7.94 mm) outside diameter tubing, 1/4" (6.0 mm) inside diametertubing.
Mounting Orientation:Vertically, with pressure connections pointing downwards.
Mechanical Working Life: Over106 switching operations.
Weight: 5.6 oz (160 g).
Enclosure Rating: NEMA 13,IP54.
Agency Approvals: CE.
EXAMPLE | ADPS | 01 | 1 | N | C | Series ADPS-01-1-N-C HVAC DifferentialPressure Switch, range 0.08-0.8" w.c., 1/2" NPT, switch rated 1.5 A@ 250 VAC, with contractor kit. |
SERIES | ADPS | HVAC Differential PressureSwitch | ||||
RANGE | 01 04 03 05 06 07 | 0.08-0.8" w.c. (20-200 Pa) 0.12-1.61" w.c. (30-400 Pa) 0.20-2.01" w.c. (50-500 Pa) 0.80-4.01" w.c. (200-1000 Pa) 2.01-10.04" w.c. (500-2050 Pa) 4.01-16.06" w.c. (1000-4000 Pa) | ||||
ELECTRICAL CONNECTION | 1 2 | 1/2" NPT M20 x 1.5 | ||||
SWITCH CONTACTS | L N | 0.4 A @ 250 VAC, (Gold Contactfor Low Voltage) 1.5 A @ 250 VAC |