Yokogawa CENTUM CS 3000 and CENTUM CS 1000 systems
Yokogawa Contact Output Module ADM52T
The specifications of I/O Modules and I/O Module Nests (for RIO) for CENTUM CS 3000 and CENTUM CS 1000 systems.
Digital I/O Modules
These modules receive and output 16 or 32 contact I/O points.
Item
Specifications
Type
Terminal type
Connector type
Model
ADM51T (*1)
ADM52T (*1)
ADM51C
ADM52C
Suffix codes
-1 :Reset action during on-line maintenance
-2 :Hold action during on-line maintenance (*2)
No. of I/O points
16 points
32 points
Output signal
Transistor contact
Contact rating
Resistive load/Inductive load: 30 V DC, 100 mA or less
Pulse width
0.1 to 7200 s: Setting at time of pulse type, pulse width mode
Pulse width resolution
20 ms
Current consumption
600 mA or less (5.0 V DC)
Function
Status output Pulse type output Pulse width output
Time proportional ON/OFF
Output function of ON/OFF status Pulse type output function of status One-shot pluse width output function Time proportional ON/OFF for Yokogawa Contact Output Module ADM52T
Signal isolation
Each point
Common minus side every 16 points
How installed
Installed in the I/O module nest
How connected
Connected to the I/O module nest terminal with M4 screws
KS2 or KS3 cable
KS9 or KS10 cable
CPU halt status / Communi- cation bus termination status
Detection time and output mode can be set when selecting the abnormal detection mode.
Terminal board
-
TE16
TE32
*1: Specify the option code “/CE1” to comply with the EMC Standards. Yokogawa Contact Output Card (RIO) ADM52T
*2: Output hold action of ADM51T-2, ADM52T-2, ADM51C-2, ADM52T, is effective in status output mode.