首页 >>> 产品目录 >>> Test & Measurement
仪表展览网 >>> 展馆展区 >>> 其他工控设备 >>> DCS系统 >>> Yokogawa Analog I/O Module NFAI841-S50
> Yokogawa Analog I/O Module NFAI841-S50

产品资料

Yokogawa Analog I/O Module NFAI841-S50[产品打印页面]

Yokogawa Analog I/O Module NFAI841-S50
  • 如果您对该产品感兴趣的话,可以
  • 产品名称:Yokogawa Analog I/O Module NFAI841-S50
  • 产品型号:NFAI841-S50
  • 产品展商:Yokogawa
  • 产品文档:无相关文档
简单介绍
Yokogawa Analog I/O Module NFAI841-S50, Yokogawa Analog I/O Module NFAI841-S50, 8-channel input, 8-channel output, non-isolated.
产品描述

Manufacturer: Yokogawa Electric Corporation 

STARDOM

FCN, FCN-500, FCN-100, FCN-RTU, FCJ

Yokogawa Analog I/O Module NFAI841-S50

Standard Specifications

Current/Voltage I/O Modules (Non-Isolated)   Yokogawa Analog I/O Module NFAI841-S50

These modules provide eight inputs and eight outputs to support up to eight loops.

Items

Specifications

Model

NFAI841(*5) (*7)

NFAB841(*5)

 

Number of I/O channels

8-channel input/8-channel output, non-isolated

8-channel input/8-channel output, non-isolated (differential input)

 

I/O signal

 

Input: 4 to 20 mA

 

Output: 4 to 20 mA

Input: 1 to 5 V (allowable common mode voltage ± 1 V or less)

 

Output: 4 to 20 mA

Allowable input current/volt- age

 

25 mA

 

 

±7.5 V

 

Overcurrent protection

Provided

 

Input resistance

Power ON

250 Ω(*1)

1 MΩ or more

Power OFF

500 kΩ or more

340 kΩ or more

Allowable load resistance

0 to 750 Ω(*3)

0 to 750 Ω

Circuit-open detection

0.65 mA or less

0.65 mA or less

Accuracy

±0.1% of full scale

±0.3% of full scale

±0.1% of full scale

±0.3% of full scale

Data refresh cycle

10 ms

Input step response time

100 ms

Output step response time

40 ms

Output fallback (*4)

Set for each channel (*3)

Set for each channel (*3)

Transmitter power supply

22.8 to 26.4 V (output current limit: 27 mA)(*2)

Setting of 2-wire or 4-wire transmitter

 

For each channel by setting pin

 

Temperature drift

Max. ±0.01 %/°C

Maximum current consump- tion

310 mA(5 V DC)

310 mA(5 V DC)

500 mA (24 V DC)

250 mA (24 V DC)

Weight

0.3 kg

External connection

Pressure clamp terminal, MIL connector cable

HART Communication(*6)

Available

*1: A voltage drop by up to 3 V may occur due to the internal protection circuit. Yokogawa Analog I/O Module NFAI841-S50
*2: Depends on the actual voltage applied by analog field power supply (24 V DC) via base module.
*3: HOLD: To hold output in which fallback is detected.
      SETV: To output a specified value when fallback is detected.
*4: Select fallback [Yes/No] for each module. Yokogawa Analog I/O Module NFAI841-S50
      If [Yes] is selected for fallback, set [HOLD/SETV] for each channel.
      Fallback detection time: 4 seconds
*5: When this I/O module is used, 24 V DC needs to be supplied to an analog field power supply terminal of the power supply module.
*6: For HART function specifications, refer to “HART Communication Functions” (GS 34P02Q53-01E).
*7: A Zener barrier is not allowed to be connected with this module. Use an isolation barrier when the module is used in intrinsically safe application.

Models and Suffix Codes   Yokogawa Analog I/O Module NFAI841-S50

 

 

Description

 

Model

 

NFAI841

Analog I/O Module

(4 to 20mA input , 4 to 20mA output, 8-channel input/8-channel output, Non-Isolated)

 

 

 

Suffix Codes

-S

Standard type

-H

With HART Communication

5

With no explosion protection

E

With explosion protection

0

Basic type

1

With ISA Standard G3 option

 

OptionCodes

/A4S00

With Pressure Clamp Terminal Block for Analog [Model : NFTA4S-00]

/A4S10

With Pressure Clamp Terminal Block for Analog (surge absorber) [Model : NFTA4S-10]

/CCC01

With Connector Cover for MIL Cable [Model : NFCCC01]


产品留言
标题
内容
联系人
联系电话
电子邮件
公司名称
联系地址
验证码
点击换一张
注:1.可以使用快捷键Alt+S或Ctrl+Enter发送信息!
2.如有必要,请您留下您的详细联系方式!