Yokogawa Relay Output Module NFDR541-P50, Yokogawa Relay Output Module NFDR541-P50, 16-channel, 24 to 110 V DC/100 to 240 V AC, Isolated. Please contact us: tekrachel @ 163.com
产品描述

Manufacturer: Yokogawa Electric Corporation

STARDOMFCN, FCN-500, FCN-100, FCN-RTU, FCJ

Yokogawa Relay Output Module NFDR541-P50 

Standard Specifications

Relay Output Module
The Relay Output Module outputs the 16-channel relay contact signals.

Yokogawa Relay Output Module NFDR541-P50

Item

Specifications

Model

NFDR541

Number of output channels

16

Rated applied voltage (*1)

24 to 110 V DC, 100 to 240 V AC, 50/60Hz

 

 

Maximum load current (*2)

Resistive load:

24 V DC: 2.0 A/channel, 48V DC: 1.0A/channel,110 V DC: 0.4 A/channel

100 V AC: 2.0 A/channel, 220 V AC: 2.0 A/channel

Inductive load:

24 V DC: 0.6 A/channel, 48V DC: 0.3A/channel,110 V DC: 0.1 A/channel

100 V AC: 1.0 A/channel, 220 V AC: 1.0 A/channel

 

Withstanding voltage

Between output signal and system: 2 kV AC

Between commons: 1.35 kV AC, common every 8-channel

Functions

Status output

 

ON/OFF status output function

 

Output fallback (*3) (*4)

HOLD: Holds the current states when the fallback action is triggered.

OFF: Resets all the output channels to off when the fallback action is triggered. NO: Performs no fallback action.

Output response time

12 ms or less (for status output)

Maximum current consumption

780 mA (5 V DC)

Weight

0.3 kg

External connection

Pressure clamp terminal

*1: NFDR541 is compliant with the EU Directives only when the voltage of 53 VDC or less is applied to its output terminal.
*2: Maximum 8 A is allowed per common. Connect a spark killer diode when driving DC relay. Yokogawa Relay Output Module NFDR541-P50
*3: Fallback detection time is 4 seconds. 
*4: HOLD, OFF, or NO should be chosen for all channels commonly. Yokogawa Relay Output Module NFDR541-P50
Note: The signals connected the same common should be the same phase when applying AC voltage.

Models and Suffix Codes 

Digital Output Module

Yokogawa Relay Output Module NFDR541-P50

 

 

Description

Model

NFDR541

Relay Output Module (16-channel, 24 to 110 V DC/100 to 240 V AC, Isolated)

 

 

Suffix Codes

-P

Standard type

5

General-purpose type with no explosion protection

E

General-purpose type with explosion protection

0

Basic type

1

With ISA Standard G3 option

Option Code

/C4S70

With Pressure Clamp Terminal Block for Digital Input [Model : NFTC4S-70]


产品留言