Manufacturer: Yokogawa Electric Corporation
Yokogawa Serial Communication Module NFLR111 NFLR121
Communication modules can be installed for FCN autonomous controllers.
Specifications Yokogawa Serial Communication Module NFLR111 NFLR121
Serial communication modules exchange data with such devices as PLC via serial communication lines.
Item Specifications Model NFLR111 NFLR121 Interface RS-232-C (2 ports) RS-422/RS-485 (2 ports) How connected Point-to-point Multipoint How communicates Half-duplex/Full-duplex (*1) How synchronizes Start-stop synchronization Communication speed 0.3, 1.2, 2.4, 4.8, 9.6, 14.4, 19.2, 28.8, 38.4, 57.6, 76.8, 115.2 kbps Transmission code ASCII/binary Character length 7/8 bits Stop bit 1/2 bits Parity check None/even/odd Transmission distance Maximum 15 m Maximum 1200 m (total extended length) Wiring connection (*2) D-sub 9-pin (female x 2) (*3) Clamped with terminal block’s M4 screws (5 poles x 2) (*4) Current consumption 500 mA Weight 0.3 kg 0.3 kg
Item
Specifications
Model
NFLR111
NFLR121
Interface
RS-232-C (2 ports)
RS-422/RS-485 (2 ports)
How connected
Point-to-point
Multipoint
How communicates
Half-duplex/Full-duplex (*1)
How synchronizes
Start-stop synchronization
Communication speed
0.3, 1.2, 2.4, 4.8, 9.6, 14.4, 19.2, 28.8, 38.4, 57.6, 76.8, 115.2 kbps
Transmission code
ASCII/binary
Character length
7/8 bits
Stop bit
1/2 bits
Parity check
None/even/odd
Transmission distance
Maximum 15 m
Maximum 1200 m (total extended length)
Wiring connection (*2)
D-sub 9-pin (female x 2) (*3)
Clamped with terminal block’s M4 screws (5 poles x 2) (*4)
Current consumption
500 mA
Weight
0.3 kg
*1: Only half-duplex communication is supported when communication of NFLR121 is done through a two-wiring system.
*2: For connection terminals and cables, refer to “Field Connection Specifications” (GS 34P02Q30-01E).
*3: Connectors are fastened using metric screw threads (M2.6).
RS-232C interface uses CD line (for input signal monitor) and CS line (for transmission of flow controls). Wiring of these signal lines is necessary.
Yokogawa Serial Communication Module NFLR111 NFLR121 Model and Suffix Codes
Description Model NFLR111 RS-232-C Communication Module (2-port, 300 bps to 115.2 kbps) Suffix Codes -S Standard Type 5 With no explosion protection E With explosion protection 0 Basic Type 1 With ISA Standard G3 option Yokogawa Serial Communication Module NFLR111 NFLR121 Description Model NFLR121 RS-422/RS-485 Communication Module (2-port, 300 bps to 115.2 kbps) Suffix Codes -S Standard Type 5 With no explosion protection E With explosion protection 0 Basic Type 1 With ISA Standard G3 option
Description
RS-232-C Communication Module
(2-port, 300 bps to 115.2 kbps)
Suffix
Codes
-S
Standard Type
5
With no explosion protection
E
With explosion protection
0
Basic Type
1
With ISA Standard G3 option
RS-422/RS-485 Communication
Module