6 Event 4. Direct Acting
7 Event 4. Reverse Acting
8 Event 5. Direct Acting
9 Event 5. Reverse Acting
10 Profile Running. Direct Acting
11 Profile Running. Reverse Acting
12 End of Profile. Direct Acting
13 End of Profile. Reverse Acting
14 Event 1 AND Alarm 1. Direct Acting
15 Event 1 AND Alarm 1. Reverse Acting
16 Event 2 AND Alarm 2. Direct Acting
17 Event 2 AND Alarm 2. Reverse Acting
18 Event 3 AND Alarm 3. Direct Acting
19 Event 3 AND Alarm 3. Reverse Acting
Parameter Name Modbus Address Access Values
(Dec) (Hex)TAIE温控器|台仪温控表FY900-301000临汾总代理商
20 Event 4 AND Alarm 4. Direct Acting
21 Event 4 AND Alarm 4. Reverse Acting
22 Event 5 AND Alarm 5. Direct Acting
23 Event 5 AND Alarm 5. Reverse Acting
Output 2 Retransmit
Minimum
2182 0x0886 R/W Limited by input range maximum/minimum
Output 2 Retransmit
Maximum
2183 0x0887 R/W Limited by input range maximum/minimum
Parameter Name Modbus Address Access Values
(Dec) (Hex)
Option Slot 3 TAIE温控器|台仪温控表FY900-301000临汾总代理商
Module Type
2192 0x0890 RO Value Module Fitted In Slot 3
0 None Fitted
1 Single Relay
2 Single SSR Driver
3 Linear mA/V DC
8 Triac
9 Dual Relay
10 Dual SSR DriverTAIE温控器|台仪温控表FY900-301000临汾总代理商
11 24VDC Transmitter PSU
255 Error (unrecognised module)
Linear mA/V DC
Output 3 Type
2193 0x0891 R/W Value Linear Output 3 Type
0 0 to 5V DC
TAIE温控器|台仪温控表FY900-301000临汾总代理商