The MC145018, when used with an ionization chamber and a small
number
of external components, will detect smoke. When smoke is sensed, an
alarm is
sounded via an external piezoelectric transducer and internal
drivers. This circuit
is designed to operate in smoke detector systems that comply with
UL217 and
UL268 specifications.
Features
• Ionization Type with On-Chip FET Input Comparator
• Piezoelectric Horn Driver
• Guard Outputs on Both Sides of Detect Input
• Input-Protection Diodes on the Detect Input
• Low-Battery Trip Point, Internally Set, can be Altered Via
External Resistor
• Detect Threshold, Internally Set, can be Altered Via External
Resistor
• Pulse Testing for Low Battery Uses LED for Battery Loading
• Comparator Output for Detect
• Internal Reverse Battery Protection
• Strobe Output for External Trim Resistors
• I/O Pin Allows Up to 40 Units to be Connected for Common
Signaling
• Supports NFPA 72, ANSi 53.41, and ISO 8201
Audible Emergency Evacuation Signals
• Power-On Reset Places IC in Standby Mode