Yokogawa Current/Voltage Input Module AAM11
GENERAL
I/O Modules and I/O Module Nests (for RIO) for CENTUM CS 3000 and CENTUM CS 1000 systems.
STANDARD SPECIFICATIONS
I/O Module Nest
Power Supply: 5.0 V DC supplied from Model AND50, ANS50, AND20, ANS20 Node Interface Unit or Model PFCS/ PFCD Field Control Station
Installation: Node Interface Unit, I/O Expansion Rack, or Model PFCS/PFCD Field Control Station.
External Dimensions: 125mm (W) x 130mm (D) x 248mm (H);
AMN51: 137.5mm (W) x 225mm (D) x 254 (H);
AMN52: 233.3mm (W) x 225mm (D) x 254mm (H)
Weight: Max. 2.5 kg (AMN52. This weight does not include I/O Modules.)
I/O Modules to be Installed in Control Stations
Models
I/O Module Names
I/O Module(s) to be Installed
CENTUM CS 1000
CENTUM CS 3000
PFCS-S, PFCD-S
PFCS-E, PFCD-E
PFCS-H, PFCD-H
AFS10S,AFS10D AFS20S,AFS20D AFG10S,AFG10D AFG20S,AFG20D
-
Analog I/O Modules
AAM10
Current/Voltage Input Module (Simplified Type)
X
AAM11
Current/Voltage Input Module
AAM11B
Current/Voltage Input Module (supports BRAIN)
AAM21
mV, Thermocouple, and RTD Input Module
AAM21J
mV, Thermocouple, and RTD Input Module (supports IEC584-1995, IEC751-1995)
APM11
Pulse Input Module
AAM50
Current Output Module
AAM51
Current/Voltage Output Module
AMC80
Multipoint Control Analog I/O Module
Relay I/O Modules
ADM15R
Relay Input Module
ADM55R
Relay Output Module
Multiplexer Modules (16 Points, Terminal Type)
AMM12T
Voltage Input Multiplexer Module
AMM22M
mV Input Multiplexer Module
AMM22T
Thermocouple Input Multiplexer Module
AMM22TJ
Thermocouple Input Multiplexer Module (supports IEC584-1995)
AMM32T
RTD Input Multiplexer Module
AMM32TJ
RTD Input Multiplexer Module (supports IEC751-1995)
AMM42T
2-Wire Transmitter Input Multiplexer Module
AMM52T
Output Multiplexer Module
Multiplexer Modules (Connector Type)
AMM12C
AMM22C
AMM25C
mV Input Multiplexer Module with Thermocouple Interface (15 Points, RJC Input port added)
AMM32C
RTD Input Multiplexer Module (16 Points)
AMM32CJ
RTD Input Multiplexer Module (16 Points, conforms to IEC751-1995)
Digital I/O Modules
ADM11T
Contact Input Module (16 Points, Terminal Type)
ADM12T
Contact Input Module (32 Points, Terminal Type)
ADM51T
Contact Output Module (16 Points, Terminal Type)
ADM52T
Contact Output Module (32 Points, Terminal Type)
ADM11C
Contact Input Module (16 Points, Connector Type)
ADM12C
Contact Input Module (32 Points, Connector Type)
ADM51C
Contact Output Module (16 Points, Connector Type)
ADM52C
Contact Output Module (32 Points, Connector Type)
Communication Modules
ACM11
RS-232C Communication Module
ACM12
RS-422/RS-485 Communication Module
ACM21
RS-232C General-purpose Communication Card
ACM22
RS-422/RS-485 General-purpose Communication Card
ACM71
Ethernet Communication Module (for PFCS/PFCD)
ACF11
Fieldbus Communication Module
ACP71
PROFIBUS Communication Module
Analog I /O Module
Current/Voltage Input Modules
Items
Specifications
Model
AAM11, AAM11B
Input signal
0 to 10 V DC
0 to 20 mA DC (*1) (*2)
(It is possible to supply power to a transmitter.)
Input resistance
1 MΩ at power-up (100 kΩ at power-down)
250 Ω
Allowable input voltage/current
-10 to 30 V DC
40 mA DC or less
Supplying power to transmitter
25.0 to 25.5 V DC (Output current limit: 60 mA DC
or less )
Auxiliary voltage output
1 to 5 V DC; Output resistance: 1 Ω or less;
Allowable load resistance: 10 kΩ or more; Signal ground is shared with system
Square root extraction
Specify whether to use square root extraction.
Accuracy
Voltage input: ±4 mV; Current input: ±16 µA; Auxiliary voltage output: ±12 mV
Effect of ambient temperature change
For 10°C change:
Voltage input: ±4 mV + ± 0.15 % of specified value
Current input: ±32 µA
Auxiliary voltage output: ±24 mV
Data update period
50 ms
Current consumption
300 mA or less (5.0 V DC)
Signal isolation
Input signals are isolated between systems
Withstanding voltage: 1500 V AC/min
How installed
Installed in the I/O Module Nest
How connected
Connected to the terminals of the I/O Module Nest with M4 screws
How input signals are specified
Specify input signals and range by software setting.