Yokogawa Small Electric Power Input Module AAM21 (mV, Thermocouple, and RTD Input Module)
GENERAL
I/O Modules and I/O Module Nests (for RIO) for CENTUM CS 3000 and CENTUM CS 1000 systems.
STANDARD SPECIFICATIONS
I/O Module Nest
Yokogawa Small Electric Power Input Module AAM21
Power Supply:
5.0 V DC supplied from Model AND50, ANS50, AND20, ANS20 Node Interface Unit or Model PFCS/
PFCD Field Control Station
Installation: Node Interface Unit, I/O Expansion Rack,
or Model PFCS/PFCD Field Control Station.
External
Dimensions: 125mm (W) x 130mm (D) x 248mm (H);
AMN51: 137.5mm (W) x 225mm (D) x 254 (H);
AMN52: 233.3mm (W) x 225mm (D) x 254mm (H)
Weight: Max. 2.5 kg
(AMN52. This weight does not include
I/O Modules.)
Installation Restrictions for I/O Module Nest
Yokogawa Small Electric Power Input Module AAM21
|
Model AMN12 High-speed Nest for Analog I/O Modules (*1)
-Always install in Nest No. 1.
-Do not install any I/O module nests in Nests No. 2 through No. 4.
-When using non-AMN12 I/O Module Nest with AMN12, always install it in Nest No. 5
Model AMM22T, AMM22TJ (*2)
-Do not install non-AMM22T, AMM22TJ I/O module
below AMM22T, AMM22TJ because AMM22T, AMM22TJ is a module for thermocouple entry. If there were a heat source below AMM22T, AMM22TJ, a reference junction compensation
error occur.
-If there is another module (heat source) below AMM22T, AMM22TJ when using 19” Rack Mountable Type,
a thermal shield must be inserted between AMM22T, AMM22TJ
and the heat source (See Figures 6 and 7).
Model AMN51 Nest for Communication Cards (*3)
-Only
one nest is installable in PFCS/PFCD.
Its position is fixed as Nest No. 2.
AMN52 Nest for PROFIBUS Communication Module
-Only one nest is installable in PFC£. Its position is fixed as Nests No. 1 and 2. AMN52 cannot be combined with AMN51.
Small Electric Power Input Module
This
module receives signals from mV,
thermocouple, RTD and potentiometer.
Yokogawa Small Electric Power Input Module AAM21
Item
|
Specifications
|
Model
|
AAM21, AAM21J (*4)
|
Input signal
|
mV
|
JIS,IEC Standard Thermocouple type K, T, J, E, B (*1), R, S, IEC Standard type N
|
RTD JIS JPt100 or
JIS Pt100 (DIN Pt100)
3-wire type
|
3-wire potentiometer’s
|
Input range
|
-50 to 150 mV
|
-50 to 150 mV
|
0 to 333 Ω
|
The total residence is within 100 to 2000 Ω, and the span is 50 % or more of the total resistance.
(*2)
|
Allowable input voltage
|
-0.5 to 4.0 V DC (between terminals B-C)
|
-
|
Input resistance
|
1 M V at power-up (3 k V at power-down)
|
-
|
Accuracy
|
±20 µV
|
±20 µV
|
±0.08 V
|
±0.2 %
|
Data update period
|
100 ms
|
Signal source resistance
|
1000 Ω or less
|
150 Ω or less (wiring resistance per wire)
|
RJC input
|
-
|
-10 to 70 °C
|
-
|
RJC accuracy
|
-
|
Within ± 1 °C (*3)
|
-
|
Measuring current
|
-
|
1 mA
|
-
|
Auxiliary voltage output
|
1 to 5 V DC (Signal ground is shared with system) Output resistance: 1 Ω or less
Allowable load resistance: 10 kΩ or more
Output range: 0.5 to 5.5 V DC Accuracy: ±12 mV
|
Burnout detection
|
Select from UP/DOWN/OFF (*5)
|
Burnout detection time
|
Within 60 sec
|
Burnout detection current
|
0.1 µA (terminal B only) (*5)
|
How installed
|
Installed in AMN11 Nest for Analog I/O Modules
|
How connected
|
Connected to the terminals of the I/O module nest with M4 screws
|
Signal isolation
|
Input signals are isolated between systems. Withstanding voltage: 1500 V AC/min
|
Current consumption
|
150 mA or less (5.0 V DC)
|
Input linearization
|
None
|
Available
|
Available
|
None
|
Effect of signal source resistance/wiring resistance (burnout is OFF)
|
1 kΩ of signal source resistance: Input conversion
± 20 µV or less
|
Wiring resistance 10 Ω for terminals A and C: In- put conversion ±40 mΩ or less (Wiring of terminals
A and C must have the same resistance)
|
-
|
Effect of ambient temperature change
|
For 10 °C change: mV input: ±40 µV
Thermocouple input: ±40 µV
RTD input: ±0.16 Ω
Potentiometer input: ±0.4 % of span
Auxiliary voltage output: ±24 mV
|
-
|
How input signals are specified
|
Specify input signals and range by software setting.
|
Option Specifications for Thermocouple
When
using the AAM21 for thermocouple
input, order the temperature compensation module for each channel.
|
|
Description
|
Model
|
AAM21, AAM21J
|
|
Option Code
|
/RJ
|
Temperature Compensation Module for Thermocouple Input
|