首页 >>> 产品目录 >>> Data Logger
仪表展览网 >>> 展馆展区 >>> 其他工控设备 >>> DCS系统 >>> Yokogawa Pulse Input Module APM11
> Yokogawa Pulse Input Module APM11

产品资料

Yokogawa Pulse Input Module APM11[产品打印页面]

Yokogawa Pulse Input Module APM11
  • 如果您对该产品感兴趣的话,可以
  • 产品名称:Yokogawa Pulse Input Module APM11
  • 产品型号:APM11
  • 产品展商:Yokogawa
  • 产品文档:无相关文档
简单介绍
Yokogawa Pulse Input Module APM11, Yokogawa Pulse Input Module APM11, CENTUM CS 3000 and CENTUM CS 1000 systems. Please contact us: tekrachel @ 163.com
产品描述

Yokogawa Pulse Input Module APM11    

Supports IEC584-1995, IEC751-1995

The specifications of I/O Modules and I/O Module Nests (for RIO) for CENTUM CS 3000 and CENTUM CS 1000 systems.  

 

Pulse Input Module

Yokogawa Pulse Input Module APM11

This module receives contact ON/OFF, voltage pulse and current pulse.

 Yokogawa Pulse Input Module APM11

Item

Specifications

Model

APM11

 

Input signal

2-wire type: Contact ON/OFF, voltage pulse, current pulse (It is possible to supply power to a transmit- ter)

3-wire type: Power supply type voltage pulse

Input frequency

0 to 10 kHz (*1)

Data update period

10 ms

Min. input pulse width

40 µs or more

 

 

 

 

Input signal level

Contact input

Relay contact, transistor contact

Detecting level open: 100 k or more; Closed: 200 or less

Contact capacity : 15 V DC, 15 mA or more at 12 V power supply; 30 V DC, 30 mA or more at 24 V

power supply

Voltage/current pulse input (The values of voltage converted from current input are as follows:) VH (high level) 3 to 24 V DC

VL (low level) -1 to 8 V DC Swing VH-VL ≥ 3 V

Signal source resistance 1 k or less

Shunt resistance

Select from 200/510/1000 /OFF

Pull-up resistance

68 k (12 V or 24 V)

Transmitter power supply

12 V DC ±10%, 35 mA or less; 24 V DC ±10%, 24 mA or less (Output current limit: 40 mA DC or less)

 

Auxiliary output signal

Output signal: Transistor contact (Open collector); Output contact capacity: 30 VDC, 30 mA or less

Signal ground is shared with the system.

Current consumption

400 mA or less (5.0 V DC)

Signal isolation

Input signals are isolated between systems. Withstanding voltage: 1500 V AC/min

How installed

Installed in the I/O Module Nest.

How connected

Connected to the terminal of the I/O Module Nest with M4 screws.

How input signal sare specified

Specify input signals and range by software setting.