Current/Voltage Output Module AAM51 Yokogawa
The specifications of I/O Modules and I/O Module Nests (for RIO) for CENTUM CS 3000 and CENTUM CS 1000 systems.
Current/Voltage Output Module
This module outputs 4 to 20 mA DC and 0 to 10 V DC.
Item
Specifications
Model
AAM51
Output signal
0 to 10 V DC
4 to 20mA DC
Output resistance
1 - or less
500 k- or more
Allowable load resistance
10 k- or more
0 to 750 -
Output range
-0.3 to 10.3 V DC
1.0 to 21.5 mA DC
Output voltage limit
-
25.5 V DC or less
Output current limit
60 mA DC or less
Output open detection
0.65 mA or less
Accuracy
Voltage output: ±12 mV
Current output: ±48 µA
Effect of ambient temperature change
For 10 °C change: Voltage output: ±4 mV + ±0.15 % of specified value
Current output: ±32 µA
Effect of load resistance change
2 k- load connection: ±4 mV
0 to 750 - load resistance change: ±16 µA
Data update period
20 ms; Step response is 150 ms
Current consumption
300 mA or less (5.0 V DC)
Signal isolation
Output signals are isolated between systems. Withstanding voltage: 1500 V AC/min
How installed
Installed in the I/O Module Nest.
How connected
Connected to the terminas of the I/O Module Nest with M4 screws.
How output signals are specified
Specify output signals and range by software setting.