Yokogawa Relay Output Module ADM55R
The specifications of I/O Modules and I/O Module Nests (for RIO) for CENTUM CS 3000 and CENTUM CS 1000 systems.
Relay Output Module Specifications
Item
Specifications
Model
ADM55R
Suffix codes
-1 : Reset action when On-Line maintenance
-2 : Hold action when On-Line maintenance (*2)
Output rating
250 V AC 1.5 A or less
125 V DC 0.1 A or less
24 V DC 1.5 A or less
Output format
A contact Between terminals AC B contact Between terminals BC
Relay operation time
10 ms or less (*1)
Relay return time
Current consumption
2 A or less (5.0 V DC)
Mounting method
Installed in the relay I/O module nest
I/O wiring
Connected to the relay I/O module nest terminal (M4)
*1: The operation and return time of the relay will be added to the communication process time of the supervisory computer. Yokogawa Relay Output Module ADM55R
*2: ADM55R-2 output is held at the status output mode only. Yokogawa Relay Output Module ADM55R