Manufacturer: Yokogawa Electric Corporation
STARDOM
FCN, FCN-500, FCN-100, FCN-RTU, FCJ
Yokogawa TC/mV Input Module NFAT141-S50
Standard Specifications
TC Input/RTD Input Modules (Isolated) These modules receive mV, thermocouple (TC) or RTD signals.
Items Specifications Model NFAT141 (*6) NFAR181 Number of input channels 16, isolated 12, isolated Input signal TC: JIS C1602:1995, IEC60584:1989 Type J, K, E, B (*1), R, S, T, N JIS C1602:1981, IEC60584:1977 Type J, K, E, B (*1), R, S, T, N IEC60584:1977 Type N mV: -100 to 150 mv, -20 to 80 mv RTD: JIS C 1604:1997, IEC 60751:1995 Pt100 (three-wire type) JIS C 1604:1989, IEC 60751:1986 Pt100 (three-wire type) JIS C 1604:1989 JPt100 (three-wire type) Switching input signals TC/mV can be set individually for CH1 to CH16. — Allowable input voltage ±5 V ±5 V Withstanding voltage Between input and system: 1500 V AC for 1 minute (*7) Between input and system: 1500 V AC for 1 minute Input resistance Power ON 2 MΩ or more Power OFF 2 MΩ or more Accuracy Thermocouple inputs: ±0.03% of full scale (for -20 to 80 mV) mV inputs: ±0.032% of full scale (for -100 to 150 mV) ±0.03% of full scale (for 0 to 400 Ω) Allowable total resistance of signal source plus wiring 1000 Ω or less 40 Ω or less (wiring resistance per wire)(*2) Effect of allowable signal source resis- tance (1000 Ω) ±20 μV — Reference junction compensation accuracy Within ±1°C (*3, 4) — Measurement current — 1 mA Temperature drift Thermocouple inputs: Max. ±30 ppm/°C mV inputs: Max. ±32 ppm/°C Max. ±30 ppm/°C Data refresh cycle 1sec Burn-out All channels can be set together. Setting: Not available/available (UP/DOWN) detection time: 60 seconds Maximum current consumption 450 mA(5 V DC) 450 mA (5 V DC) Weight 0.2 kg External connection Pressure clamp terminal, MILconnector cable (*5)(*7) Pressure clamp terminal *1: Type B does not carry out temperature compensation and can not measure under 44°C. *2: Each wiring resistance should be equal. Yokogawa TC/mV Input Module NFAT141-S50 *5: Use a MIL connector cable for only mV input. *6: The NFAT141 thermocouple input module imposes limitations in installation. See “Restrictions and Precautions on Installation”. *7: The withstanding voltage for using MIL connector cable depends on the electrical specifications of its cable. If you are using KMS40 cable, withstanding voltage of between input and system is 500 V AC for 1 minute.
Items
Specifications
Model
NFAT141 (*6)
NFAR181
Number of input channels
16, isolated
12, isolated
Input signal
TC: JIS C1602:1995, IEC60584:1989
Type J, K, E, B (*1), R, S, T, N
JIS C1602:1981, IEC60584:1977
IEC60584:1977
Type N
mV: -100 to 150 mv, -20 to 80 mv
RTD: JIS C 1604:1997, IEC 60751:1995
Pt100 (three-wire type)
JIS C 1604:1989, IEC 60751:1986
Pt100 (three-wire type) JIS C 1604:1989
JPt100 (three-wire type)
Switching input signals
TC/mV can be set individually for CH1 to
CH16.
—
Allowable input voltage
±5 V
Withstanding voltage
Between input and system: 1500 V AC for 1
minute (*7)
Between input and system: 1500 V AC for 1 minute
Input resistance
Power ON
2 MΩ or more
Power OFF
Accuracy
Thermocouple inputs:
±0.03% of full scale (for -20 to 80 mV)
mV inputs:
±0.032% of full scale (for -100 to 150 mV)
±0.03% of full scale (for 0 to 400 Ω)
Allowable total resistance of signal source plus wiring
1000 Ω or less
40 Ω or less (wiring resistance per wire)(*2)
Effect of allowable signal source resis-
tance (1000 Ω)
±20 μV
Reference junction compensation accuracy
Within ±1°C (*3, 4)
Measurement current
1 mA
Temperature drift
Thermocouple inputs: Max. ±30 ppm/°C
mV inputs: Max. ±32 ppm/°C
Max. ±30 ppm/°C
Data refresh cycle
1sec
Burn-out
All channels can be set together.
Setting: Not available/available (UP/DOWN)
detection time: 60 seconds
Maximum current consumption
450 mA(5 V DC)
450 mA (5 V DC)
Weight
0.2 kg
External connection
Pressure clamp terminal, MILconnector cable
(*5)(*7)
Pressure clamp terminal
Models and Suffix Codes
Description
NFAT141
TC/mV Input Module (16-channel, Isolated)
Suffix Codes
-S
Standard type
5
With no explosion protection
E
With explosion protection
0
Basic type
1
With ISA Standard G3 option
Option Codes
/T4S00
With Pressure Clamp Terminal Block for Thermocouple/mV [Model: NFTT4S-00]
/T4S10
With Pressure Clamp Terminal Block for Thermocouple/mV (surge absorber) [Model: NFTT4S-10]
/CCC01
With Connector Cover for MIL Cable [Model: NFCCC01]