Manufacturer: Yokogawa Electric Corporation
Yokogawa Distributed Control System (DCS) FCU AFV30D-S41152
Hardware Specifications
Yokogawa Distributed Control System (DCS) FCU AFV30D-S41152
For the installation specifications and the environmental conditions common to the systems, refer to “Vnet/IP System Overview (Vnet/IP Edition)”.
Processor
VR5432 (133 MHz)
Main Memory Capacity
32 Mbyte
Memory Protection During Power Failure
Battery
Battery Back-up for Main Memory: Max. 72 hours
Battery Recharge Time: Min. 48 hours
FCU Status Contact Output
2 terminals (NC, C)
Contact Points open during FCU failure
Contact Rating: 30 V DC, max. 0.3 A
Communication Interface
Vnet/IP Interface: Dual-redundant
For more details, refer to “Integrated Production Control System CENTUM VP System Overview (Vnet/IP Edition)” (GS 33K01A10-50E).
No. of Node Units Connectable
Max. 14/FCU
The total number of ESB Bus Node Units and ER Bus Node Units that can be connected to FCU are 14 or less. (ESB Bus Node Units: 9 or less)
LFS1500 allows up to 3 nodes, and can be expanded to 14 if LFS1550 Application capacity Expansion Package (for AFV10 ) is added.
To connect a node unit to the FCU, a Node Unit Expansion License (Option code: /NDEL) is required for the node unit.
Module configuration
Power Supply Module (PW481 or PW482 or PW484):
Two modules in case of a dual-redundant configuration.
Processor Module (CP451): Two modules in case of a dual-redundant configuration.
I/O Modules(*1): Max. 8
*1: Non-standard components.
ESB Bus Node Units Connection
When connecting an ESB Bus Node Unit to FCU, install ESB Bus Coupler Module (EC401) on FCU. EC401 must be installed in slot 7 and slot 8. For the dual-redundant configuration of the processor modules, EC401 must be installed in both slot 7 and slot 8.
In case ESB Bus has a single configuration, EC401 must be installed in slot 7 and keep slot 8 empty.
ER Bus Node Units Connection
When connecting an ER Bus Node Unit to FCU, install ER Bus Interface Master Module (EB401) on FCU.
To make single configuration, EB401 must be installed in an odd-number slot, and keep empty the right side of the installed EB401.
See “ER Bus Interface Master Module (for FIO)” (GS 33K50F40-50E) for further information.
Power Supply
Voltage: 100-120 V AC, Frequency: 50/60 Hz
Voltage: 220-240 V AC, Frequency: 50/60 Hz
Voltage: 24 V DC
Specify with Suffix Codes. Yokogawa Distributed Control System (DCS) FCU AFV30D-S41152
Power Consumption
100-120 V AC: 200 VA
220-240 V AC: 230 VA
24 V DC: 5.5 A
Weight
Approx. 7 kg (AFV10S)
Approx. 8 kg (AFV10D)
Mounting
Yokogawa Distributed Control System (DCS) FCU AFV30D-S41152
19-inch Rack Mounting:
Rack mount (8 x M5 screws)
Insulation bush (accessory)
Connection
Power Supply: M4 screw terminal connection Grounding: M4 screw terminal connection Contact Output: M4 screw terminal connection Network: Connect UTP cable (CAT5e or better) to Layer 2 switch.
Regulatory Compliance
For the detailed information of following standards, see “System Overview (Vnet/IP Edition)” (GS 33K01A10-50E).
Safety Standards
[CSA] (for 100-120 V AC power supply)
[CE Marking] (for 220-240 V AC power supply)
EMC Conformity Standards Yokogawa Distributed Control System (DCS) FCU AFV30D-S41152
[CE Marking] (for 220-240 V AC and 24 V DC power supply)
[C-Tick Marking] (for 220-240 V AC and 24 V DC power supply)
[KC Marking] (for 220-240 V AC and 24 V DC power supply)
Standards for Hazardous Location Equipment
[FM Non-Incendive] (for 100-120 V AC, 220-240 V AC and 24 V DC power supply)
[Type n] (for 24 V DC power supply)
Standard Accessories
The FCU is delivered with the following standard accessories.
Yokogawa Distributed Control System (DCS) FCU AFV30D-S41152
Parts Names
|
PartsNumbers
|
Description
|
Quantity
|
Remarks
|
Insulating bush
|
S9049PM
|
–
|
8
|
Accessory
|
Models and Suffix Codes
Duplexed Field Control Unit
Yokogawa Distributed Control System (DCS) FCU AFV30D-S41152
|
|
Description
|
Model
|
AFV30D
|
Duplexed Field Control Unit (for Vnet/IP and FIO, 19-inch Rack Mountable)
|
Suffix
Codes
|
-S
|
Standard type
|
4
|
Dual-redundant Vnet/IP, dual-redundant power supply
|
1
|
Always 1
|
1
|
100 - 120 V AC power supply (*1)
|
2
|
220 - 240 V AC power supply (*1)
|
4
|
24 V DC power supply (*1)
|
5
|
Basic type with no explosion protection
|
6
|
With ISA Standard G3 option and no explosion protection
|
E
|
Basic type with explosion protection
|
F
|
With ISA Standard G3 option and explosion protection
|
1
|
LFS1700 Control function for field control station
(for AFV30£/AFV40£, Vnet/IP and FIO) <for CP461>
|
Option
Codes
|
/HKU
|
With HKU interface (*2)
|
/ATDOC
|
Explosion Protection Manual (*3)
|
Note: These products are subject to the Export Administration Regulations (EAR) by the United States Department of Commerce, Bureau of Industry and Security (BIS). It is not possible to export or reexport these products to Iran, Cuba, North Korea, Syria, and Sudan.
*1: To meet the safety standards and EMC standards, the unit must be installed in a keyed metallic cabinet.
*2: When used in combination with ACUKT£, specify this option code “/HKU.”
*3: Select the option code “/ATDOC” to follow the ATEX Directive for use in potentially explosive atmospheres.