Manufacturer: Yokogawa Electric Corporation
Yokogawa Temperature Controller TC10-NHCRRRDSF
General
The TC10 is a compact single loop temperature controller with easy-to-read 3 dynamic colors led display. The short depth of the controller helps save instrument panel space. The TC10 supports easy configuration with codes for quick start-up.
Yokogawa Temperature Controller TC10-NHCRRRDSF
Functional Specifications
Control Specifications
Control Mode: On/Off heating, On/Off cooling, On/Off with neutral zone (H/C),
PID heating, PID cooling, PID double action (H/C),Auto-tuning and Self-tuning algorithms, Overshoot control
Alarm Functions
Absolute high/low, Absolute inside/outside the band, Yokogawa Temperature Controller TC10
Sensor break, Deviation high/low, Deviation inside/ outside the band.
They are combined with Not active at power up, Latched, Acknowledgeable, and Not active at set point change for Deviation alarm.
Yokogawa Temperature Controller TC10-NHCRRRDSF
Digital Input Functions
Alarm reset, Alarm acknowledge, Hold of the measured value, Stand-by mode, Manual mode,
Heat with SP1 and Cool with SP2, Sequential set point selection, SP1/SP2 selection,
Binary selection of the set point, Work in parallel with Up/down key. Yokogawa Temperature Controller TC10
Communication Function
Interface type: Isolated (50 V) RS-485
Protocol: Modbus RTU
Baud rate: 1200, 2400, 9600, 19200, 38400 bps
Byte format: 8bit with no parity, one stop bit.
Instrument address: 1 to 25
Yokogawa Temperature Controller TC10-NHCRRRDSF
Model and Suffix Code
Model Code
|
Suffix codes
|
Description
|
TC10
|
-N
|
o
|
C
|
o
|
o
|
o
|
D
|
o
|
F
|
|
Temperature Controller
|
Fixed code
|
-N
|
|
|
|
|
|
|
|
|
|
Always "-N"
|
Power supply
|
L
|
|
|
|
|
|
|
|
|
24 VAC/DC (Custom order)
|
H
|
|
|
|
|
|
|
|
|
100 to 240 VAC
|
Fixed code
|
C
|
|
|
|
|
|
|
|
Always "C"
|
OUT1 - 3
|
R
|
N
|
N
|
|
|
|
|
Relay output for ON/OFF control
|
R
|
R
|
R
|
|
|
|
|
Relay output with 2 alarm relays, for ON/OFF or Heat/Cool control with 1 alarm
|
V
|
N
|
N
|
|
|
|
|
DC Output for SSR
|
V
|
R
|
R
|
|
|
|
|
DC Output for SSR with 2 alarm relays or DCV and Relay output for Heat/Cool control with 1 alarm
|
V
|
V
|
R
|
|
|
|
|
2 DCV outputs for SSR with 1 Relay
(Custom order)
|
A
|
R
|
R
|
|
|
|
|
Analog output with 2 alarm Relays, or analog output and Relay output for Heat/Cool control with 1 alarm
|
IN/OUT4(Fixed code)
|
D
|
|
|
|
Always "D" - Selectable I/O (logic input / 12 V SSR drive output / 12VDC
20 mA transmitter power supply
|
Serial communication
|
S
|
|
|
RS485 Modbus
|
N
|
|
|
None
|
Fixed code
|
F
|
|
Always “F”
|
Option Code
|
/GK
|
Panel gasket for IP65
|