Manufacturer: Yokogawa Electric Corporation
Yokogawa Base Plate A2BN5D-221C0 for Barrier (for N-IO, P+F Barrier)
A2BN5D Base Plate for Barrier
This base plate communicates with the node interface unit via an F-SB bus by connecting a field signal to a terminal on the I.S. barrier mounted on.
The Base plate for barrier, one of the components of the N-IO I/O unit (for Barrier) which is defined as A2ZN5DC for the system model, enables to mount I/O modules and various I.S. barriers from Pepperl+Fuchs GmbH (P+F). This base plate has a field connection terminal (spring clamp terminal) for connecting the field signals. If it is necessary to disconnect the signal line between the field device and the I.S. barrier, disconnect the signal line outside the base plate for barrier. Yokogawa Base Plate A2BN5D-221C0 for Barrier (for N-IO, P+F Barrier)
The I/O modules can be mounted in a single or dual-redundant configuration. Channels on the base plate are available to connect up to 16 I.S. barriers. The base plate has a system power supply and a field power supply interface and has a function to supply power to the I/O modules from the node interface unit via the power supply cable for base plate (A2KPB00) as well as to supply field power to the I.S. barriers by connecting the specified power
line. The tables below show the I/O modules and I.S. barriers that can be mounted on the base plate.
I/O modules (for N-IO)
A2MMM843, A2MDV843
P+F’s I.S. barriers for Yokogawa Base Plate A2BN5D-221C0 for Barrier (for N-IO, P+F Barrier)
HiC2025 (272017), HiC2025ES (292850)
HiC2031 (272020), HiC2031HC (226027)
HiC2831 (272022)
HiC2873Y1 (279013), HiC2883 (243729)
HiC2081 (275178)
H-CP
Connection F-SB bus [BUS1/BUS2]
Connected with the F-SB bus cable (A2KLF00)
Weight for Yokogawa Base Plate A2BN5D-221C0 for Barrier (for N-IO, P+F Barrier)
Approx. 0.93 kg
Model and Suffix Codes for Yokogawa Base Plate A2BN5D-221C0 for Barrier (for N-IO, P+F Barrier)
Model A2BN5D Base plate for barrier (for N-IO, P+F barrier)
Suffix Codes
-2 For both DIN rail and wall mount type
2 Spring clamp terminal for field wiring
1 With explosion protection (*1) (*2) (*3)
C I.S. wiring (Left) (*4)
D I.S. wiring (Right) (*4)
0 Always 0
Note: With ISA standard G3 by default.
Note: In Korea, provide DOCIM33J01J3008KO to comply with the KCs IS for intrinsic safety of explosion-protection.
*1: A2BN5D style S1 cannot be installed in the hazardous area.
*2: In Korea, A2BN5D is used only for intrinsic safety of explosion-protection, but it and cannot be installed in the hazardous area.
*3: In Eurasian Economic Union, A2BN5D is used only for intrinsic safety of explosion-protection and but it cannot be installed in the hazardous area.
*4: The P+F I.S. barrier can be mounted. The I.S. circuit is placed on the left for A2BN5D-221C0 and on the right for A2BN5D-221D0 of the base plate. (For details, refer to the external dimensions).