Manufacturer: Yokogawa Electric Corporation
Yokogawa DCS Module AAI143-H53
STANDARD SPECIFICATIONS
Current Input Modules (Isolated) This module inputs 4 to 20 mA. It can be used in dual redundant configuration.
Yokogawa Analog Input Module AAI143-H53 Yokogawa DCS Module AAI143-H53
Items Specifications Model AAI143 (*1) Number of input channels 16, isolated Input signal 4 to 20 mA Allowable input current 24 mA Withstanding voltage Between input and system: 1500 V AC For 1 minute (*4) Input resistance Power ON 270 Ω (20 mA) to 350 Ω (4 mA) (*2) Power OFF 500 kΩ or more Accuracy ±16 μA Data update period 10 ms Transmitter power supply 19.0 V or more (at 20 mA) 25.5 V or less (at 0 mA) (output current limit: 25 mA) (*5) Setting of 2-wire or 4-wire transmitter For each channel by setting pin Drift due to ambient temperature change ±16 μA/10˚C Maximum current consumption 230 mA (5 V DC) , 540 mA (24 V DC) Weight 0.3 kg External communication Pressure clamp terminal, MIL connector cable, Dedicated cable (KS1) HART communication (*3) Available
Items
Specifications
Model
AAI143 (*1)
Number of input channels
16, isolated
Input signal
4 to 20 mA
Allowable input current
24 mA
Withstanding voltage
Between input and system: 1500 V AC For 1 minute (*4)
Input resistance
Power ON
270 Ω (20 mA) to 350 Ω (4 mA) (*2)
Power OFF
500 kΩ or more
Accuracy
±16 μA
Data update period
10 ms
Transmitter power supply
19.0 V or more (at 20 mA) 25.5 V or less (at 0 mA) (output current limit: 25 mA) (*5)
Setting of 2-wire or 4-wire transmitter
For each channel by setting pin
Drift due to ambient temperature change
±16 μA/10˚C
Maximum current consumption
230 mA (5 V DC) , 540 mA (24 V DC)
Weight
0.3 kg
External communication
Pressure clamp terminal, MIL connector cable, Dedicated cable (KS1)
HART communication (*3)
Available
*1: This module Yokogawa Analog Input Module AAI143-H53 does not allow a Zener barrier to be connected. If the module is to be used in intrinsically safe applications, use an isolation barrier.
*2: Viewed from the terminals, module input resistance is, depending on the current flowing:
250 Ω +( voltage drop (0.4 V maximum) in the input protection circuit)/(current value)
*3: When installing the module Yokogawa Analog Input Module AAI143-H53 with HART function to a remote node, the firmware of EB401 must be Rev 2 or later.For HART function specifications, refer to “HART Communication Package (for A□I□□□-H) (GS 33Q03L70-31E).”
*4: The withstanding voltage for using the dedicated cable is 500 V AC (between the input signal and the system).The withstanding voltage for using MIL connector cable depends on the electrical specifications of its cable.
MODELS AND SUFFIX CODES
Description Model AAI143 Analog Input Module (4 to 20 mA, 16-channel, Isolated) Suffix Codes -S Standard type -H With digital communication (HART protocol) 5 With no explosion protection E With explosion protection 0 Basic type 3 With ISA Standard G3 option and temperature (-20 to 70 °C) option Option Codes /K4A00 With KS Cable Interface Adapter (For connecting AEA4D Terminal Board) [Model: ATK4A-00] /A4S00 With Pressure Clamp Terminal Block [Model: ATA4S-00] /A4S10 With Pressure Clamp Terminal Block (surge absorber) [Model: ATA4S-10] /A4D00 With Dual Pressure Clamp Terminal Block [Model: ATA4D-00] /A4D10 With Dual Pressure Clamp Terminal Block (surge absorber) [Model: ATA4D-10] /CCC01 With Connector Cover for MIL Cable [Model: ACCC01]
Description
AAI143
Analog Input Module (4 to 20 mA, 16-channel, Isolated)
Suffix Codes
-S
Standard type
-H
With digital communication (HART protocol)
5
With no explosion protection
E
With explosion protection
0
Basic type
3
With ISA Standard G3 option and temperature (-20 to 70 °C) option
Option Codes
/K4A00
With KS Cable Interface Adapter (For connecting AEA4D Terminal Board) [Model: ATK4A-00]
/A4S00
With Pressure Clamp Terminal Block [Model: ATA4S-00]
/A4S10
With Pressure Clamp Terminal Block (surge absorber) [Model: ATA4S-10]
/A4D00
With Dual Pressure Clamp Terminal Block [Model: ATA4D-00]
/A4D10
With Dual Pressure Clamp Terminal Block (surge absorber) [Model: ATA4D-10]
/CCC01
With Connector Cover for MIL Cable [Model: ACCC01]