Yokogawa Optical ESB Bus Repeater Slave Module ANT502-E0/HU1B
产品描述

Yokogawa Optical ESB Bus Repeater Slave Module ANT502-E0/HU1B

Models ANT401, ANT502 Optical ESB Bus Repeater Module for 5km (for AFV30S, AFV30D/AFV40S, AFV40D)

 Manufacturer: Yokogawa Electric Corporation

Control System: CENTUM VP

The Optical ESB Bus Repeater Module converts the ESB bus to an optical signal and transmits it. The ESB bus transmission distance can be extended within the range of up to 5 km by connecting the ANT401 Optical ESB Bus Repeater Master Module and ANT502 Optical ESB Bus Repeater Slave Module with an optical fiber cable.


- ANT401 Optical ESB Bus Repeater Master Module for 5 km
This module can be installed in the Field Control Unit (AFV30S, AFV30D/AFV40S, AFV40D), Unit for Optical ESB Bus Repeater Module (ANT10U), ESB Bus Node Unit (ANB10S, ANB10D), and Optical ESB Bus Node Unit (ANB11S, ANB11D).
To connect the ANT401 to the ESB bus, specify “Connector unit for ESB Bus” (option code “/CU1N”).
To terminate the ESB bus at the ANT401, specify “Connector unit with terminator for ESB Bus” (option code “/CU1T”).

- ANT502 Optical ESB Bus Repeater Slave Module for 5 km
ANT502 or ANT512 are installed as standard in the Optical ESB Bus Node Unit (ANB11) as a slave module of the optical ESB bus. It can also be installed in the Unit for Optical ESB Bus Repeater Module (ANT10U).
To connect the ANT502 to the ESB bus, specify “Connector unit with ESB Bus connector” (option code “/BU1A” or “HU1A”). To not connect the ANT502 to the ESB bus, specify “Connector unit” (option code “/BU1B” or “/HU1B”).
To monitor the temperatures and fans in the cabinet, specify “With HKU interface” (option code “/HU1A” or “/HU1B”).

Standard Specifications
Function: ESB bus optical transport
Connection type: chain type connection and star type connection
Maximum number of connectable stages: 2 (for chain type connection)
Maximum number of connection: 8 (for chain type and star type connection)
Maximum transmission distance: 5 km (when using ANT401, ANT502, and ANB11S/ANB11D)
Current consumption: 0.5 A (for ANT401/ANT502)
Weight: 0.25 kg (main body only) (for ANT401/ANT502)