Yokogawa ProSafe-RS Analog Output Module SDV541-S63
STANDARD SPECIFICATIONS
Output Module
Item
Specifications
Model
SDV541
Number of outputs
16-channel, module isolation
Output voltage
24 V DC
Output voltage drop
1 V maximum
External power supply rating
24 V DC, 3.4 A minimum
External power supply
24 V DC + 20 % / -10 % (*1) Current capacity: 3.4 A
Maximum leak current at output off status
1.6 mA
Output format
Current source
Maximum load current
0.2 A/output line (3.2 A in total output line) (*2)
Minimum load current
35 mA
Load resistance range
120 to 685 Ω (*3)
Output response time
30 ms maximum
Withstand voltage
2 kV AC (between output signal lines and system), 16-point input lines collectively connected (negative lines) (*4)
Current consumption
300 mA maximum (5 V DC)
150 mA maximum (24 V DC)
Weight
0.26 kg (For pressure clamp terminal block or MIL cable)
0.31 kg (With dedicated signal cable interface adapter)
External connection
Pressure clamp terminal
MIL cable
Dedicated signal cable (AKB331, AKB651)
*1: External power supply of SDV541-S53 style code S1 is 24 V DC ± 5%.
*2: Do not exceed this value, including the case of inrush/variation of the load current.
*3: Resistance value of the load for both ON and OFF state, including the field wiring resistance.
*4: When connecting SDV541-S53 and SED4D terminal board using AKB331 dedicated signal cable, the withstand voltage is 500
V AC (between output signal lines and system). If MIL connector cables are used, the withstand voltage depends on their cable’s electrical specifications.
Description
Digital Output Module (16-channel, module isolation)
Suffix Codes
-S
Standard type
5
For pressure clamp terminal block or MIL cable with no explosion protection
6
With signal cable interface adapter and no explosion protection (*1)
E
For pressure clamp terminal block or MIL cable with explosion protection
F
With signal cable interface adapter and explosion protection (*1)
3
With ISA standard G3 and temperature (-20 to 70 °C)
Option Codes
/B4S00
With pressure clamp terminal block for digital output (without surge absorber) [Model: STB4S-00]
/B4S10
With pressure clamp terminal block for digital output (with surge absorber) [Model: STB4S-10]
/B4D00
Dual-redundant pressure clamp terminal block for digital output (without surge absorber) (*2) [Model: STB4D-00]
/B4D10
Dual-redundant pressure clamp terminal block for digital output (with surge absorber) (*2) [Model: STB4D-10]
/PRP
With prevention pin of false insertion (*3)
/CCC01
With connector cover for MIL cable (for flat ribbon cable) [Model: SCCC01]
/CCC02
With connector cover for MIL cable (for discrete wire cable) [Model: SCCC02]
*1: When SDV541-S53-S63 or -SF3 is selected, you cannot choose the option code for a pressure clamp terminal block and MIL
cable connector.
*2: When this module is used in dual-redundant configuration, order an additional module with the same specification but without option codes. Yokogawa ProSafe-RS Analog Output Module SDV541-S63
*3: When SDV541-S53-S63 or -SF3 is selected, you can choose the option code for prevention pin of false insertion.