Yokogawa Centum VP, Yokogawa DCS
Yokogawa Node Unit ANB10S, ANB10D
The ESB Bus Node Unit has an interface function that communicates the analog I/O signals and contact I/O signals of a field with a Field Control Unit (FCU) via an ESB bus, as well as a function that supplies power to the I/O Modules.
This node units are connected to FCU via ESB bus.
Hardware specifications
Yokogawa Node Unit ANB10S, ANB10D
For the installation specifications and environmental conditions that are common to the systems, refer to 'FIO System Overview (for Vnet/IP) (GS 33K50KF10-50E).'
No. of Node Units Connectable
Vnet/IP
Field Control Unit
|
Database
|
Total Number of ESB Bus Units (ANB10 ) and Optical ESB Bus Node Units (ANB11 ) Connectd per FCU
|
AFV30
AFV40
(*1)
|
Control Function for Field Control Station (LFS1700)
|
Max. 3
|
Control Function for Field Control Station (LFS1700) plus Node Expansion Package (LFS1750-V1)
|
Max. 9
|
Control Function for Field Control Station (LFS1700) plus Node Expansion Package (LFS1750-V2)
|
Max. 13
|
*1: Up to 11 node units per 1 cabinet can be installed in AFV40 .
Field Control Unit
|
Database
|
ESB Bus Node Units (ANB10 ) Connected per FCU
|
ER Bus Node Units (ANR10 )Connected per FCU
|
Total Number of ESB Bus Node Units ( ANB10 ) and ER Bus Node Units (ANR10 )Connected per FCU
|
AFV10
|
Control Function for Field Control Station (LFS1500)
|
Max. 3
|
Max. 3
|
Max. 3
|
Control Function for Field Control Station (LFS1500) plus Application Capacity Expansion Package (LFS1550)
|
Max. 9
|
Max. 14
|
Max. 14
|
Vnet
Field Control Unit
|
Database
|
ESB Bus Node Units (ANB10 ) Connected per FCU
|
ER Bus Node Units (ANR10 )Connected per FCU
|
Total Number of ESB Bus Node Units ( ANB10 ) and ER Bus Node Units (ANR10 ) Connected per FCU
|
AFF50
|
Control Function for Compact Field Control Station (LFS1350)
|
Max. 3
|
Max. 3
|
Max. 3
|
AFG30
AFG40
|
Control Function for Enhance Field Control Station (LFS1330) with Node expanded databases
|
Max. 10
|
Max. 14
|
Max. 15
|
Others
|
Max. 10 (*1)
|
Max. 9 (*1)
|
Max. 10 (*1)
|
*1: In Case of AFG81 and AFG82 ,there are total number with SIO Nest (for CENTUM V or CENTUM-XL).
Total number of SIO: Max 5/FCU
ESB Bus Node Connection
Yokogawa Node Unit ANB10S, ANB10D
When connecting an ESB Bus Node Unit to FCU, install ESB Bus Couple Module (EC401 or EC402) to FCU (*1).
EC401 or EC402 must be installed in slot 7 and slot 8. To make single configuration, EC401 or EC402 must be installed in slot 7, and slot 8 must be empty.
*1: AFV30 , AFV40 , AFV10 , or AFF55 .
Power Supply
Yokogawa Node Unit ANB10S, ANB10D
Specify with Suffix Codes
Voltage: 100-120 V AC, Frequency: 50/60 Hz
Voltage: 220-240 V AC, Frequency: 50/60 Hz
Voltage: 24 V DC
Electric Power Consumption
100-120 V AC: 200 VA, 120 W
220-240 V AC: 230 VA, 120 W
24 V DC: 5.5 A
Weight
10 kg (including 8 I/O Modules)
Mounting
19-inch Rack Mounting
Rack mount (M5 x 4 screws)
Insulation bash (accessory)