Yokogawa ESB Bus Node Unit ANB10D-425/CU2N/NDEL
The ESB Bus Node Unit has an interface function that communicates the analog I/O signals and contact I/O signals of a field with a Field Control Unit (FCU) via an ESB bus, as well as a function that supplies power to the I/O Modules.
This node units are connected to FCU via ESB bus.
Hardware specifications
Yokogawa ESB Bus Node Unit ANB10D-425/CU2N/NDEL
For the installation specifications and environmental conditions that are common to the systems, refer to 'FIO System Overview (for Vnet/IP) (GS 33K50KF10-50E).'
No. of Node Units Connectable
Vnet/IP
Field Control Unit
|
Database
|
Total Number of ESB Bus Units (ANB10 ) and Optical ESB Bus Node Units (ANB11 ) Connectd per FCU
|
AFV30
AFV40
(*1)
|
Control Function for Field Control Station (LFS1700)
|
Max. 3
|
Control Function for Field Control Station (LFS1700) plus Node Expansion Package (LFS1750-V1)
|
Max. 9
|
Control Function for Field Control Station (LFS1700) plus Node Expansion Package (LFS1750-V2)
|
Max. 13
|
*1: Up to 11 node units per 1 cabinet can be installed in AFV40 .
Field Control Unit
|
Database
|
ESB Bus Node Units (ANB10 ) Connected per FCU
|
ER Bus Node Units (ANR10 )Connected per FCU
|
Total Number of ESB Bus Node Units ( ANB10 ) and ER Bus Node Units (ANR10 )Connected per FCU
|
AFV10
|
Control Function for Field Control Station (LFS1500)
|
Max. 3
|
Max. 3
|
Max. 3
|
Control Function for Field Control Station (LFS1500) plus Application Capacity Expansion Package (LFS1550)
|
Max. 9
|
Max. 14
|
Max. 14
|
Vnet
Field Control Unit
|
Database
|
ESB Bus Node Units (ANB10 ) Connected per FCU
|
ER Bus Node Units (ANR10 )Connected per FCU
|
Total Number of ESB Bus Node Units ( ANB10 ) and ER Bus Node Units (ANR10 ) Connected per FCU
|
AFF50
|
Control Function for Compact Field Control Station (LFS1350)
|
Max. 3
|
Max. 3
|
Max. 3
|
AFG30
AFG40
|
Control Function for Enhance Field Control Station (LFS1330) with Node expanded databases
|
Max. 10
|
Max. 14
|
Max. 15
|
Others
|
Max. 10 (*1)
|
Max. 9 (*1)
|
Max. 10 (*1)
|
*1: In Case of AFG81 and AFG82 ,there are total number with SIO Nest (for CENTUM V or CENTUM-XL).
Total number of SIO: Max 5/FCU
ESB Bus Node Connection
Yokogawa ESB Bus Node Unit ANB10D-425/CU2N/NDEL
When connecting an ESB Bus Node Unit to FCU, install ESB Bus Couple Module (EC401 or EC402) to FCU (*1).
EC401 or EC402 must be installed in slot 7 and slot 8. To make single configuration, EC401 or EC402 must be installed in slot 7, and slot 8 must be empty.
*1: AFV30 , AFV40 , AFV10 , or AFF55 .
Power Supply
Yokogawa ESB Bus Node Unit ANB10D-425/CU2N/NDEL
Specify with Suffix Codes
Voltage: 100-120 V AC, Frequency: 50/60 Hz
Voltage: 220-240 V AC, Frequency: 50/60 Hz
Voltage: 24 V DC
Electric Power Consumption of Yokogawa ESB Bus Node Unit ANB10D-425/CU2N/NDEL
100-120 V AC: 200 VA, 120 W
220-240 V AC: 230 VA, 120 W
24 V DC: 5.5 A
Weight for Yokogawa ESB Bus Node Unit ANB10D-425/CU2N/NDEL
10 kg (including 8 I/O Modules)
Mounting
19-inch Rack Mounting
Rack mount (M5 x 4 screws)
Insulation bash (accessory)