Yokogawa ER Bus Node Unit Node Unit ANR10D-415/NDEL
The ER Bus Node Unit has an interface function that communicates the analog I/O signals and contact I/O signals of a field with a Field Control Unit (FCU), as well as a function that supplies power to the I/O Modules.
Yokogawa ER Bus Node Unit Node Unit ANR10D-415/NDEL
Hardware specifications
No. of Node Units Connectable
Vnet/IP
Field Control Unit
|
Database
|
ESB Bus Node Units (ANB10 ) Connected per FCU
|
ER Bus Node Units (ANR10 )Connected per FCU
|
Total Number of ESB Bus Node Units ( ANB10 ) and ER Bus Node Units (ANR10 )Connected per FCU
|
AFV10
|
Control Function for Field Control Station (LFS1500)
|
Max. 3
|
Max. 3
|
Max. 3
|
Control Function for Field Control Station (LFS1500) plus Application Capacity Expansion Package (LFS1550)
|
Max. 9
|
Max. 14
|
Max. 14
|
Vnet
Field Control Unit
|
Database
|
ESB Bus Node Units (ANB10 ) Connected per FCU
|
ER Bus Node Units (ANR10 )Connected per FCU
|
Total Number of ESB Bus Node Units ( ANB10 ) and ER Bus Node Units (ANR10 ) Connected per FCU
|
AFF50
|
Control Function for Compact Field Control Station (LFS1350)
|
Max. 3
|
Max. 3
|
Max. 3
|
AFG30
AFG40
|
Control Function for Enhance Field Control Station (LFS1330) with Node expanded databases
|
Max. 10
|
Max. 14
|
Max. 15
|
Others
|
Max. 10 (*1)
|
Max. 9 (*1)
|
Max. 10 (*1)
|
1: In Case of AFG81 and AFG82 ,there are total number with SIO Nest (for CENTUM V or CENTUM-XL).
Total number of SIO: Max 5/FCU
Remote Node Connection
Yokogawa ER Bus Node Unit Node Unit ANR10D-415/NDEL
ER Bus: Max.4/FCU
When connecting a ER Bus Node Unit to a ESB Bus Node Unit or Field Control Unit, install ER Bus Interface Master Module (EB401) to the ESB Bus Node Unit or Field Control Unit.
To make single configuration, EB401 must be installed in an odd-number slot, and make a space on the right side of the installed EB401.
See “ER Bus Interface Master Module (for FIO)” (GS 33K50F40-50E) for further information.
Power Supply
Specify with Suffix Codes
Voltage: 100-120 V AC, Frequency: 50/60 Hz
Voltage: 220-240 V AC, Frequency: 50/60 Hz
Voltage: 24 V DC
Electric Power Consumption
100-120 V AC: 200 VA, 120 W
220-240 V AC: 230 VA, 120 W
24 V DC: 5.5 A
Weight
10 kg (including 8 I/O Modules)
Mounting
19-inch Rack Mounting
Rack mount (M5 x 4 screws)
Insulation bash (accessory)
Regulatory Compliance
For the detailed information of following standards, see “System Overview” (GS 33K01A10-50E).
Safety Standards
[CSA] (for 100-120 V AC and 24 V DC power supply)
[CE Marking] (for 100-120 V AC, 220-240 V AC and 24 V DC power supply)
EMC Conformity Standards
[CE Marking] (for 100-120 V AC, 220-240 V AC and 24 V DC power supply)
[C-Tick Marking] (for 220-240 V AC and 24 V DC power supply)
[KC Marking] (for 100-120 V AC, 220-240 V AC and 24 V DC power supply)
Standards for Hazardous Location Equipment
[CSA Non-Incendive] (for 100-120 V AC and 24 V DC power supply)
[FM Non-Incendive] (for 100-120 V AC, 220-240 V AC and 24 V DC power supply)
[Type n] (for 24 V DC power supply)