STANDARD SPECIFICATIONS
I/O Module Nest
Yokogawa Nest AMN52
Power Supply:
5.0 V DC supplied from Model AND50, ANS50, AND20, ANS20 Node Interface Unit or Model PFCS/
PFCD Field Control Station
Installation: Node Interface Unit, I/O Expansion Rack,
or Model PFCS/PFCD Field Control Station.
External
Dimensions: 125mm (W) x 130mm (D) x 248mm (H);
AMN51: 137.5mm (W) x 225mm (D) x 254 (H);
AMN52: 233.3mm (W) x 225mm (D) x 254mm (H)
Weight: Max. 2.5 kg
(AMN52. This weight does not include
I/O Modules.)
Yokogawa Nest AMN52
Models
|
Names
|
CS 1000
|
CS 3000
|
Installation Restrictions
(See next page)
|
AFS10S,AFS10D
AFG10S,AFG10D AFG20S,AFG20D
|
PFCS PFCD
|
AMN11
|
Nest for Analog I/O Modules
|
X
|
X
|
X
|
|
AMN12
|
High-Speed Nest for Analog I/O Modules
|
|
X
|
|
(*1)
|
AMN21
|
Nest for Relay I/O Modules
|
X
|
X
|
X
|
|
AMN31
|
Nest for Terminal I/O Modules
|
X
|
X
|
X
|
(*2)
|
AMN32
|
Nest for Connector I/O Modules
|
X
|
X
|
X
|
|
AMN33
|
Nest for Communication Modules
|
X
|
X
|
X
|
|
AMN34
|
Nest for Multipoint Control Analog I/O Modules
|
X
|
X
|
X
|
|
AMN51
|
Nest for Communication Cards
|
X
|
|
X
|
(*3)
|
AMN52
|
Nest for PROFIBUS Communication Module
|
X (*5)
|
|
X (*5)
|
(*4)
|
Installation Restrictions for I/O Module Nest
Yokogawa Nest AMN52
|
Model AMN12 High-speed Nest for Analog I/O Modules (*1)
-Always install in Nest No. 1.
-Do not install any I/O module nests in Nests No. 2 through No. 4.
-When using non-AMN12 I/O Module Nest with AMN12, always install it in Nest No. 5
Model AMM22T, AMM22TJ (*2)
-Do not install non-AMM22T, AMM22TJ I/O module
below AMM22T, AMM22TJ because AMM22T, AMM22TJ is a module for thermocouple entry. If there were a heat source below AMM22T, AMM22TJ, a reference junction compensation
error occur.
-If there is another module (heat source) below AMM22T, AMM22TJ when using 19” Rack Mountable Type,
a thermal shield must be inserted between AMM22T, AMM22TJ
and the heat source (See Figures 6 and 7).
Model AMN51 Nest for Communication Cards (*3)
-Only
one nest is installable in PFCS/PFCD.
Its position is fixed as Nest No. 2.
AMN52 Nest for PROFIBUS Communication Module
-Only one nest is installable in PFC£. Its position is fixed as Nests No. 1 and 2. AMN52 cannot be combined with AMN51.
I/O Modules to be Installed in Control Stations
Yokogawa Nest AMN52
Models
|
I/O Module Names
|
I/O Module(s) to be Installed
|
CENTUM CS 1000
|
CENTUM CS 3000
|
PFCS-S, PFCD-S
|
PFCS-E, PFCD-E
|
PFCS-H, PFCD-H
|
AFS10S,AFS10D AFS20S,AFS20D AFG10S,AFG10D AFG20S,AFG20D
|
-
|
Analog I/O Modules
|
AAM10
|
Current/Voltage Input Module (Simplified Type)
|
X
|
X
|
X
|
X
|
AAM11
|
Current/Voltage Input Module
|
X
|
X
|
X
|
X
|
AAM11B
|
Current/Voltage Input Module (supports BRAIN)
|
X
|
X
|
X
|
X
|
AAM21
|
mV, Thermocouple, and RTD Input Module
|
X
|
X
|
X
|
X
|
AAM21J
|
mV, Thermocouple, and RTD Input Module (supports IEC584-1995, IEC751-1995)
|
X
|
X
|
X
|
X
|
APM11
|
Pulse Input Module
|
X
|
X
|
X
|
X
|
AAM50
|
Current Output Module
|
X
|
X
|
X
|
X
|
AAM51
|
Current/Voltage Output Module
|
X
|
X
|
X
|
X
|
AMC80
|
Multipoint Control Analog I/O Module
|
X
|
X
|
X
|
X
|
-
|
Relay I/O Modules
|
ADM15R
|
Relay Input Module
|
X
|
X
|
X
|
X
|
ADM55R
|
Relay Output Module
|
X
|
X
|
X
|
X
|
-
|
Multiplexer Modules (16 Points, Terminal Type)
|
AMM12T
|
Voltage Input Multiplexer Module
|
X
|
X
|
X
|
X
|
AMM22M
|
mV Input Multiplexer Module
|
X
|
X
|
X
|
X
|
AMM22T
|
Thermocouple Input Multiplexer Module
|
X
|
X
|
X
|
X
|
AMM22TJ
|
Thermocouple Input Multiplexer Module (supports IEC584-1995)
|
X
|
X
|
X
|
X
|
AMM32T
|
RTD Input Multiplexer Module
|
X
|
X
|
X
|
X
|
AMM32TJ
|
RTD Input Multiplexer Module (supports IEC751-1995)
|
X
|
X
|
X
|
X
|
AMM42T
|
2-Wire Transmitter Input Multiplexer Module
|
X
|
X
|
X
|
X
|
AMM52T
|
Output Multiplexer Module
|
X
|
X
|
X
|
X
|
-
|
Multiplexer Modules (Connector Type)
|
AMM12C
|
Voltage Input Multiplexer Module
|
X
|
X
|
X
|
X
|
AMM22C
|
mV Input Multiplexer Module
|
X
|
X
|
X
|
X
|
AMM25C
|
mV Input Multiplexer Module with Thermocouple Interface (15 Points, RJC Input port added)
|
X
|
X
|
X
|
X
|
AMM32C
|
RTD Input Multiplexer Module (16 Points)
|
X
|
X
|
X
|
X
|
AMM32CJ
|
RTD Input Multiplexer Module (16 Points, conforms to IEC751-1995)
|
X
|
X
|
X
|
X
|
-
|
Digital I/O Modules
|
ADM11T
|
Contact Input Module (16 Points, Terminal Type)
|
X
|
X
|
X
|
X
|
ADM12T
|
Contact Input Module (32 Points, Terminal Type)
|
X
|
X
|
X
|
X
|
ADM51T
|
Contact Output Module (16 Points, Terminal Type)
|
X
|
X
|
X
|
X
|
ADM52T
|
Contact Output Module (32 Points, Terminal Type)
|
X
|
X
|
X
|
X
|
ADM11C
|
Contact Input Module (16 Points, Connector Type)
|
X
|
X
|
X
|
X
|
ADM12C
|
Contact Input Module (32 Points, Connector Type)
|
X
|
X
|
X
|
X
|
ADM51C
|
Contact Output Module (16 Points, Connector Type)
|
X
|
X
|
X
|
X
|
ADM52C
|
Contact Output Module (32 Points, Connector Type)
|
X
|
X
|
X
|
X
|
-
|
Communication Modules
|
ACM11
|
RS-232C Communication Module
|
X
|
X
|
X
|
X
|
ACM12
|
RS-422/RS-485 Communication Module
|
X
|
X
|
X
|
X
|
ACM21
|
RS-232C General-purpose Communication Card
|
-
|
X
|
X
|
-
|
ACM22
|
RS-422/RS-485 General-purpose Communication Card
|
-
|
X
|
X
|
-
|
ACM71
|
Ethernet Communication Module (for PFCS/PFCD)
|
-
|
X
|
X
|
-
|
ACF11
|
Fieldbus Communication Module
|
X
|
X
|
X
|
X
|
ACP71
|
PROFIBUS Communication Module
|
-
|
X
|
X
|
-
|
X: Installable
- : Not installed