Manufacturer: Yokogawa Electric Corporation
STARDOM: FCN, FCN-500, FCN-100, FCN-RTU, FCJ
Yokogawa Frequency Input Module NFAF135-S50
Standard Specifications
Frequency Input Module(Isolated Channels) This module is with eight channels input. It measures pulse and converts it into number of revolutions or frequency.
Items
Specifications
Model
NFAF135
Number of input channels
8, isolated channels
Input signal (*1)
Contact ON/OFF, voltage pulse (rectangular wave)
Input frequency
0.1 Hz to 10 kHz (*2)
Frequency accuracy
0.1% of reading
Withstanding voltage (*3)
Between input and system: 500 V AC for 1 minute, between channels: 500 V AC for 1 minute
Minimum input pulse width
40 μs
Input signal level
Contact input
Open/close levels of relay contact and transistor contact
Open: 100 kΩ or more, Close: 200 Ω or less
Contact capacity
When supplying 12 V DC: 15 V DC 15 mA or more
When supplying 24 V DC: 30 V DC 30 mA or more
Voltage pulse input
VH-VL (swing value): 3 V or more
VH (high level): 3 to 24 V DC VL (low level): -1 to 8 V DC
Signal source resistance: 1 kΩ or less
Shunt resistance
Select from OFF/1000 Ω. (Open when power is OFF) (*1)
Pull-up resistance
68 kΩ (12 V DC or 24 V DC)
Data refresh cycle
10ms
Field power supply (*4)
Can select 24 V DC/12 V DC.
Limiter value 12 V DC ±10 %: 40 mA,
24 V DC ±10 %: 30 mA
Maximum current consumption
300 mA (5 V DC), 400 mA (24 V DC)
Weight
0.3 kg
External connection
Pressure clamp terminal, MIL connector cable (*3)
Models and Suffix Codes
Description Model NFAF135 Frequency Input Module (8-channel, Contact ON/OFF, Voltage Pulse, 0.1 Hz to 10kHz, Isolated channels) Suffix Codes -S Standard type 5 With no explosion protection E With explosion protection 0 Basic type 1 With ISA Standard G3 option OptionCodes /13S00 With Pressure Clamp Terminal Block for Frequency [Model: NFTI3S-00] /13S10 With Pressure Clamp Terminal Block for Frequency (surge absorber) [Model: NFTI3S-10] /CCC01 With Connector Cover for MIL Cable [Model: NFCCC01]
Description
Frequency Input Module (8-channel, Contact ON/OFF, Voltage Pulse, 0.1 Hz to 10kHz, Isolated channels)
Suffix Codes
-S
Standard type
5
With no explosion protection
E
With explosion protection
0
Basic type
1
With ISA Standard G3 option
OptionCodes
/13S00
With Pressure Clamp Terminal Block for Frequency [Model: NFTI3S-00]
/13S10
With Pressure Clamp Terminal Block for Frequency (surge absorber) [Model: NFTI3S-10]
/CCC01
With Connector Cover for MIL Cable [Model: NFCCC01]